江阴市土壤源热泵系统的性能研究及适宜性评价
Alternative TitlePerformance Research and Suitability Evaluation of a Ground Coupled Heat Pump of Construction in Jiangyin
刘广平1,2,3,4; 骆超1,2,3; 龚宇烈1,2,3; 邱泽晶5,6; 郑鑫5,6
2017-08
Source Publication新能源进展
ISSN2095-560X
Volume5Issue:4Pages:315-324
Abstract针对江苏省江阴市某休闲会所商用建筑的土壤源热泵系统,采用TRNSYS软件模拟并分析了冬夏季供暖空调期土壤源热泵系统COP的变化。结果表明,在地埋管深度为100m情况下,热泵系统的供热季节性能参数为3.31,供冷季节性能参数为3.37。对该地区的土壤源热泵系统采用层次分析法构建了评价体系,进行适宜性评价指标计算,并对土壤源热泵系统和常规冷热源系统的经济性和环境性进行了对比分析。与常规冷热源系统相比,土壤源热泵系统年运行费用是常规冷热源系统的75.6%,一次能源利用率高出13%,节约标煤量达1.71t,温室气体减排量为4.47t,全年能效比为2.74。土壤源热泵系统具有明显的节能、经济、环保优势,适宜性较好。
Other AbstractAccording to a ground coupled heat pump(GCHP)system for a commercial building in Jiangyin city,Jiangsu province,a model was built based on TRNSYS software to simulate and analysis its coefficient of performance(COP)under different working conditions.The results showed that the heating season performance factor(HSPF)of heat pump system was3.31in summer and the seasonal energy-efficiency ratio(SEER)was3.37in winter when the pipe buried depth was100meters.Analytic hierarchy process(AHP)was used to evaluation the suitability of GCHP system,and compared with the conventional system in terms of economic and environmental performance.It was found that the operating cost of GCHP system was75.6%of the conventional system,the primary energy ratio was13%higher,save coal amount was1.71tons,greenhouse gas reductions was4.47tons,and the all-yearly energy-efficiency ratio was2.74.The GCHP system presents high suitability regarding its advantages in energy-saving,economic,and environment protection.
Keyword土壤源热泵 数值模拟 季节性能系数 适宜性评价 ground coupled heat pump numerical simulation seasonal coefficient of performance suitability evaluation
DOI10.3969/j.issn.2095-560X.2017.04.012
Language中文
Citation statistics
Document Type期刊论文
Identifierhttp://ir.giec.ac.cn/handle/344007/16609
Collection中国科学院广州能源研究所
Corresponding Author龚宇烈
Affiliation1.中国科学院广州能源研究所,广州510640;
2.中国科学院可再生能源重点实验室,广州510640;
3.广东省新能源和可再生能源研究开发与应用重点实验室,广州510640;
4.中国科学院大学,北京100049;
5.南瑞集团公司(国网电力科学研究院),南京211000;
6.南瑞(武汉)电气设备与工程能效测评中心,武汉430074
First Author AffilicationGuangZhou Institute of Energy Conversion,Chinese Academy of Sciences
Recommended Citation
GB/T 7714
刘广平,骆超,龚宇烈,等. 江阴市土壤源热泵系统的性能研究及适宜性评价[J]. 新能源进展,2017,5(4):315-324.
APA 刘广平,骆超,龚宇烈,邱泽晶,&郑鑫.(2017).江阴市土壤源热泵系统的性能研究及适宜性评价.新能源进展,5(4),315-324.
MLA 刘广平,et al."江阴市土壤源热泵系统的性能研究及适宜性评价".新能源进展 5.4(2017):315-324.
Files in This Item: Download All
File Name/Size DocType Version Access License
江阴市土壤源热泵系统的性能研究及适宜性评(1076KB)期刊论文出版稿开放获取CC BY-NC-SAView Download
Related Services
Recommend this item
Bookmark
Usage statistics
Export to Endnote
Google Scholar
Similar articles in Google Scholar
[刘广平]'s Articles
[骆超]'s Articles
[龚宇烈]'s Articles
Baidu academic
Similar articles in Baidu academic
[刘广平]'s Articles
[骆超]'s Articles
[龚宇烈]'s Articles
Bing Scholar
Similar articles in Bing Scholar
[刘广平]'s Articles
[骆超]'s Articles
[龚宇烈]'s Articles
Terms of Use
No data!
Social Bookmark/Share
File name: 江阴市土壤源热泵系统的性能研究及适宜性评价.pdf
Format: Adobe PDF
All comments (0)
No comment.
 

Items in the repository are protected by copyright, with all rights reserved, unless otherwise indicated.