Abstract | 近年来,随着IT行业的快速发展,通信基站空调系统能耗急剧增大.与传统蒸汽压缩式空调系统相比,自然冷源降温技术耗电量小、节能效果显著.本文针对在济南某基站采用自然冷源替代传统蒸汽压缩式空调用于机房降温的可行性进行了分析.结果表明,测试周期内,在4℃温差的自控启动条件下,降温主机的平均能效比可以达到12.78左右,且随着环境温度的降低,室内外温差、主机供冷率和阶段平均能效比均呈增大趋势.此外,通过对测试数据的回归拟合,给出了主机供冷率与室内外温差以及环境温度的经验关联式.实验结果表明,自然冷源降温是一种值得推广的机房节能技术. |
Other Abstract | In recent years, with the rapid development of IT industry, the energy consumption of air conditioning system in telecommunication base stations has increased dramatically. Compared with the traditional vapor compression air conditioning system, the free cooling technology has advantages in relative smaller electricity consumption and remarkable energy-saving. In this paper, the feasibility of using free cooling unit instead of traditional vapor compression air conditioning systems for room cooling in one of base stations is analyzed in Jinan. The results show that, in the testing period, under the condition of automatic temperature control at 4oC, the average EER of the cooling unit can reach about 12.78; with ambient temperature decreasing, the indoor and outdoor temperature difference, cooling unit power output and stage average EER are increased. In addition, through the test data regression, a fitting correlation between the cooling unit power output, indoor and outdoor temperature difference and ambient temperature is also given. The experimental results show the free cooling technology is worthy of promotion in the field of base station energy saving. |
Keyword | 自然冷源 基站 能效比 节能 free cooling base station EER energy saving |
DOI | 10.3969/j.issn.2095-560X.2017.06.011 |
Language | 中文 |
Citation statistics | |
Document Type | 期刊论文 |
Identifier | http://ir.giec.ac.cn/handle/344007/16602 |
Collection | 中国科学院广州能源研究所 |
Corresponding Author | 王显龙 |
Affiliation | 1.中国移动通信集团设计院有限公司山东分公司,济南250101; 2.中国科学院广州能源研究所,广州510640; 3.宝武集团广东韶关钢铁有限公司,广东韶关512000 |
Recommended Citation GB/T 7714 | 牛琳,王显龙,李华山,等. 济南某基站自然冷源降温系统实验研究[J]. 新能源进展,2017,5(6):484-488. |
APA | 牛琳.,王显龙.,李华山.,廉永旺.,卜宪标.,...&陶寿松.(2017).济南某基站自然冷源降温系统实验研究.新能源进展,5(6),484-488. |
MLA | 牛琳,et al."济南某基站自然冷源降温系统实验研究".新能源进展 5.6(2017):484-488. |
Files in This Item: | Download All | |||||
File Name/Size | DocType | Version | Access | License | ||
济南某基站自然冷源降温系统实验研究.pd(909KB) | 期刊论文 | 出版稿 | 开放获取 | CC BY-NC-SA | View Download |
Items in the repository are protected by copyright, with all rights reserved, unless otherwise indicated.
Edit Comment