GIEC OpenIR  > 中国科学院广州能源研究所
济南某基站自然冷源降温系统实验研究
Alternative TitleExperiment Study on Free Cooling System with Temperature Decreasing of Communication Base Station in Jinan
牛琳1; 王显龙2; 李华山2; 廉永旺2; 卜宪标2; 王令宝2; 陶寿松3
2017-12
Source Publication新能源进展
ISSN2095-560X
Volume5Issue:6Pages:484-488
Abstract近年来,随着IT行业的快速发展,通信基站空调系统能耗急剧增大.与传统蒸汽压缩式空调系统相比,自然冷源降温技术耗电量小、节能效果显著.本文针对在济南某基站采用自然冷源替代传统蒸汽压缩式空调用于机房降温的可行性进行了分析.结果表明,测试周期内,在4℃温差的自控启动条件下,降温主机的平均能效比可以达到12.78左右,且随着环境温度的降低,室内外温差、主机供冷率和阶段平均能效比均呈增大趋势.此外,通过对测试数据的回归拟合,给出了主机供冷率与室内外温差以及环境温度的经验关联式.实验结果表明,自然冷源降温是一种值得推广的机房节能技术.
Other AbstractIn recent years, with the rapid development of IT industry, the energy consumption of air conditioning system in telecommunication base stations has increased dramatically. Compared with the traditional vapor compression air conditioning system, the free cooling technology has advantages in relative smaller electricity consumption and remarkable energy-saving. In this paper, the feasibility of using free cooling unit instead of traditional vapor compression air conditioning systems for room cooling in one of base stations is analyzed in Jinan. The results show that, in the testing period, under the condition of automatic temperature control at 4oC, the average EER of the cooling unit can reach about 12.78; with ambient temperature decreasing, the indoor and outdoor temperature difference, cooling unit power output and stage average EER are increased. In addition, through the test data regression, a fitting correlation between the cooling unit power output, indoor and outdoor temperature difference and ambient temperature is also given. The experimental results show the free cooling technology is worthy of promotion in the field of base station energy saving.
Keyword自然冷源 基站 能效比 节能 free cooling base station EER energy saving
DOI10.3969/j.issn.2095-560X.2017.06.011
Language中文
Citation statistics
Document Type期刊论文
Identifierhttp://ir.giec.ac.cn/handle/344007/16602
Collection中国科学院广州能源研究所
Corresponding Author王显龙
Affiliation1.中国移动通信集团设计院有限公司山东分公司,济南250101;
2.中国科学院广州能源研究所,广州510640;
3.宝武集团广东韶关钢铁有限公司,广东韶关512000
Recommended Citation
GB/T 7714
牛琳,王显龙,李华山,等. 济南某基站自然冷源降温系统实验研究[J]. 新能源进展,2017,5(6):484-488.
APA 牛琳.,王显龙.,李华山.,廉永旺.,卜宪标.,...&陶寿松.(2017).济南某基站自然冷源降温系统实验研究.新能源进展,5(6),484-488.
MLA 牛琳,et al."济南某基站自然冷源降温系统实验研究".新能源进展 5.6(2017):484-488.
Files in This Item: Download All
File Name/Size DocType Version Access License
济南某基站自然冷源降温系统实验研究.pd(909KB)期刊论文出版稿开放获取CC BY-NC-SAView Download
Related Services
Recommend this item
Bookmark
Usage statistics
Export to Endnote
Google Scholar
Similar articles in Google Scholar
[牛琳]'s Articles
[王显龙]'s Articles
[李华山]'s Articles
Baidu academic
Similar articles in Baidu academic
[牛琳]'s Articles
[王显龙]'s Articles
[李华山]'s Articles
Bing Scholar
Similar articles in Bing Scholar
[牛琳]'s Articles
[王显龙]'s Articles
[李华山]'s Articles
Terms of Use
No data!
Social Bookmark/Share
File name: 济南某基站自然冷源降温系统实验研究.pdf
Format: Adobe PDF
All comments (0)
No comment.
 

Items in the repository are protected by copyright, with all rights reserved, unless otherwise indicated.