基于协调控制SVG的低压配网三相负荷不平衡治理技术
其他题名The Control Technology of Three-Phase Unbalance Load in Low Voltage Distribution Networks Based on Coordinated Controlled SVGs
邓惠华1; 李国良1; 周晓明1; 李汉荣1; 王浩2
2017-07
发表期刊电工技术学报
ISSN1000-6753
卷号32期号:S1页码:75-83
摘要针对集中式静止无功发生器(SVG)补偿系统补偿效果单一、不含通信功能的分布式SVG补偿系统补偿容量不能智能分配的问题,提出基于协调控制SVG的低压配网三相负荷不平衡补偿系统。该补偿系统引入通信总线,采用协调控制方法,使低压线路下游接入的SVG可利用补偿其下游不平衡电流后的剩余容量,依次对上游SVG不足容量进行补偿,该补偿形成的逆向潮流可进一步减轻各节点的低电压问题。该补偿系统既可以充分利用各SVG的补偿容量,同时也综合地解决了配电变压器电流不平衡、节点低电压等问题。在Matlab/Simulink数字仿真软件下进行了该补偿系统补偿效果的仿真,结果证明了该补偿系统的准确性。在四种不同负荷情况下比较采用四种不同补偿系统的低压配网配电变压器二次侧不平衡电流和各节点电压降,结果表明该补偿系统的效果最佳。
其他摘要Concentralized static var generator(SVG)compensation system has single compen-sation effect and distributed SVG compensation system without communication function can notdistribute SVG’s compensation capacities intelligently.Aiming at these problems,a compensationsystem based on SVGs’coordinated control strategy was proposed for three-phase unbalance load inlow voltage distribution network.Communication bus and coordinated control strategy are introducedin the proposed system.After compensating the downstream unbalance current,the residual capacity ofthe downstream SVG is used to compensate the upstream SVGs in sequence.The low voltage problemof each node is further reduced by the reverse power flows from the downstream SVG to the upstreamSVG.And then SVG’s capacity in the proposed compensation system can be fully used.Meanwhile,theproblems of the distribution transformer’s unbalance current and the node’s low voltage aresynthetically solved.Simulations for actual effect evaluation of the proposed compensation systemwere done in Matlab/Simulink.Validity of the proposed system is confirmed by the simulation.In fourdifferent load cases,four different compensation systems were applied in low voltage distribution station,respectively.Unbalance currents of distribution transformer secondary and node voltage dropsin these cases were compared.Comparison results show that proposed compensation system has thebest compensation effect.
关键词低压配网 三相负荷不平衡 配电变压器运行 协调控制 静止无功发生器 电能质量 Low voltage distribution networks three-phase load unbalance distribution transformer operation coordinated control static var generator (SVG) power quality
DOI10.19595/j.cnki.1000-6753.tces.L70726
语种中文
引用统计
文献类型期刊论文
条目标识符http://ir.giec.ac.cn/handle/344007/16598
专题中国科学院广州能源研究所
通讯作者王浩
作者单位1.广东电网有限责任公司惠州供电局,惠州516001;
2.中国科学院广州能源研究所,广州510640
推荐引用方式
GB/T 7714
邓惠华,李国良,周晓明,等. 基于协调控制SVG的低压配网三相负荷不平衡治理技术[J]. 电工技术学报,2017,32(S1):75-83.
APA 邓惠华,李国良,周晓明,李汉荣,&王浩.(2017).基于协调控制SVG的低压配网三相负荷不平衡治理技术.电工技术学报,32(S1),75-83.
MLA 邓惠华,et al."基于协调控制SVG的低压配网三相负荷不平衡治理技术".电工技术学报 32.S1(2017):75-83.
条目包含的文件 下载所有文件
文件名称/大小 文献类型 版本类型 开放类型 使用许可
基于协调控制SVG的低压配网三相负荷不平(1957KB)期刊论文出版稿开放获取CC BY-NC-SA浏览 下载
个性服务
推荐该条目
保存到收藏夹
查看访问统计
导出为Endnote文件
谷歌学术
谷歌学术中相似的文章
[邓惠华]的文章
[李国良]的文章
[周晓明]的文章
百度学术
百度学术中相似的文章
[邓惠华]的文章
[李国良]的文章
[周晓明]的文章
必应学术
必应学术中相似的文章
[邓惠华]的文章
[李国良]的文章
[周晓明]的文章
相关权益政策
暂无数据
收藏/分享
文件名: 基于协调控制SVG的低压配网三相负荷不平衡治理技术.pdf
格式: Adobe PDF
所有评论 (0)
暂无评论
 

除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。